Commercial kitchen hood sizing: m³/h and plenum
Size a commercial kitchen hood from kW × coefficient, pick slot, baffle or water-drained plenum by equipment, plan make-up air. Worked 5 m line example.
"Eyeballing it" is the most expensive method
Two hood mistakes we see most in the field:
- "2 m × 1 m should be enough for this kitchen" — eyeballed
- "We'll reuse the hood from the old kitchen" — cross-kitchen recycling
Both end up the same: peak service, kitchen air stagnates, heat won't pull, oil drips from the hood. The operator usually says "spin the fan faster" — and then kitchen pressure drops, doors won't open, burners don't burn cleanly.
A hood needs engineering math. This post shares the field formula and TS EN 16282 reference.
Base formula: fuel capacity × coefficient
Exhaust capacity (m³/h):
Exhaust = Σ (Equipment kW × Equipment coefficient) × Draw factor
Equipment coefficients (m³/h per kW)
Each equipment type has a different emission character:
- Pizza oven (gas): 30 m³/h per kW (high heat, low grease)
- Pizza oven (electric): 20 m³/h per kW
- Range (gas): 35 m³/h per kW (combustion gas + vapour)
- Plate grill: 40 m³/h per kW (grease + vapour)
- Fryer: 50 m³/h per kW (highest grease emission)
- Convection oven: 25 m³/h per kW
- Steamer: 30 m³/h per kW (steam-heavy)
- Range stove (multi-zone): 35-40 m³/h per kW
Draw factor
Based on plenum type and line geometry:
- Slot-type plenum: 1.0
- Baffle filter: 1.1
- Corner-mounted hood: 1.2 (sidewall losses)
- Island hood: 1.3 (four sides open, high loss)
Worked example
5 m line, restaurant kitchen:
- 4-burner gas range: 28 kW → 28 × 35 = 980 m³/h
- 800 mm plate grill: 18 kW → 18 × 40 = 720 m³/h
- Twin-tank fryer: 20 kW → 20 × 50 = 1000 m³/h
- Convection oven: 12 kW → 12 × 25 = 300 m³/h
Total: 3000 m³/h × 1.1 (baffle filter) = 3300 m³/h exhaust
Spec a 3500 m³/h hood (about 5% buffer).
Equipment type → plenum type
The plenum is the section of the hood the air is drawn through before it reaches the duct: an open slot, a baffle filter bank or a water-drained channel. It changes the draw factor above (1.0 for slot, 1.1 for baffle), so it is chosen together with the m³/h figure, not afterwards:
High heat, low grease (pizza oven, convection)
Slot plenum suffices. No grease vapour, just hot air. Filter optional.
High grease (fryer, plate, range)
Baffle filter mandatory. Condenses grease, channels to drain. Non-negotiable for annual fire-safety inspection.
Steam cooking (steamer, pasta cooker)
Water-drained plenum — channels condensate out the side. Without it, the hood drips.
If one hood covers mixed equipment, design zoned plenums: slot over pizza, baffle over fryer, water-drain over steamer. One hood visually, three zones underneath.
Make-up air: the forgotten half
Most operators size the exhaust but forget make-up air. Result:
- Kitchen goes under pressure
- Dining-room door won't open on its own
- Hood "chokes" — fan runs but can't pull
- Back-drafts and odours from toilets and drains
Make-up air rule: about 80-85% of exhaust as supply. For the example above: 3300 × 0.82 = 2700 m³/h make-up air.
Two methods:
- Standalone make-up air fan — fresh air from roof/façade, side-blown to hood
- Compensated hood (integrated make-up air) — separate plenum at the hood face
Recommendation: for hoods over 2500 m³/h, use integrated make-up air. In hot, humid climates, supply must be conditioned (filtered + cooled).
TS EN 16282: reference standard
In Turkey, commercial-kitchen ventilation is governed by TS EN 16282, seven parts:
- Part 1: General requirements (air flow, pressure)
- Part 2: Exhaust air capacity calculation (the formula above)
- Part 3: Grease filters and aerosol separators
- Part 4: Make-up air and air distribution
- Part 5: Fire safety (damper, sprinkler)
- Part 6: Hood construction details
- Part 7: Maintenance and inspection intervals
CE-marked hoods are built to this standard. Every hood we design in the field is verified against TS EN 16282-2.
Common mistakes
What we see most:
- Hood smaller than equipment line — line is 5 m, hood is 4 m. Side-loss reaches 30%
- Single exhaust point — long lines pile air on one side, the other end can't pull
- Missing or undersized make-up air — correct on paper, fails in service
- Skipped grease-filter maintenance — uncleaned filters create fire risk
- Tying into the building HVAC — hood needs its own duct; shared duct carries kitchen odour to the dining room
Conclusion
A hood is not eyeballed equipment — it's the backbone of the kitchen's airflow. Correct sizing:
- Sum kW × coefficient per equipment
- Multiply by draw factor
- Add 5-10% buffer
- Plan make-up air at 80-85%
- Verify TS EN 16282 compliance
Share your equipment list; we'll calculate hood + make-up air together. A wrong number costs five times the hood in annual energy + fire risk + service losses.